Parameter | Measured Values |
Total Harmonics Distorition | THD-V, THD-I |
Voltage Harmonics | Up to 55st harmonics (L-N and L-L] |
Current Harmonics | Up to 55st harmonics |
Active Power | P1, P2, P3, ΣP |
Reactive Power | Q1, Q2, Q3, ΣQ |
Q | S1, S2, S3, ΣS |
Power Factor | True PF, cos φ (of each phase) |
Voltage | phase-to-phase |
phase-to-neutral | |
(min, max & average values are saved) | |
Current | I1, I2, I3, ΣI (min, max & demand are saved) |
Frequency | F1, F2 ,F3 (min, max & average) |
Energy | ∑kWh (import & export) |
∑kVARh (inductive & Capacitive) | |
Relay Output | 2 Relay outputs (adjustable), 1 digital input |
Irregularties | voltage and current İmplances |
Screen | 71.5 X 61.5 Custom Design Glass LCD. |
Communication | RS485 Modbus RTU |
Event logs | High voltage, low voltage, power interruption, Voltage and current implances, high current, THD-V & THD-I limits |
Real time Clock | Date and time can be set |
Memory | You can delete energy values, demands records and event logs. |
Password | Menu is password protected |
Parameter | Value |
Operating Voltage | 85V - 240 AC |
Operating Frequency | 50 / 60 Hz |
Operating Power | <10VA |
Operating Temperature | -20°C…..55°C |
Input Voltage (L-N) | 1V - 330VAC |
Voltage Measuring Range | 1V - 600kV |
Input Current | 1mA - 5,5A |
Current Measuring Range | 1mA - 50.000A |
Voltage, Current, Accuracy | %±0.2 |
Active Energy Accuracy | %±0.5 |
Reactive Energy Accuracy | %±1 |
Supported Connection | 3P4W |
Current Transformer Ratio | 1….5000 |
Voltage Transformer Ratio | 1,0….9999 |
Harmonic Voltage | 3 - 55 |
Harmonic Current | 3 - 55 |
Real Time Clock | > 5 Year |
Contact Output | 2A / 250V AC [Resistive Load] |
Digital Input | 9V - 24V DC |
Weight | <300Gr |
Protection Class | IP41[Front Panel], IP20[Body] |
Panel Hole Measurement | 91mm x 91mm |
Connection Type | Plug-in Terminal Connection |
Cable Diameter | 1.5mm² |
Mounting | Assembly to panel front cover |
Working Altitude | <2000 meter |