Window-type current transformer with sealable terminal cover,
suitable for primary currents from 1000A to 4000A AC;
available in 1A or 5A AC secondary current;
and accuracy classes Class 0.1, 0.2S, 0.2, 0.5S, 0.5 or Class 1.0.
TK10010005209
TK100 | ||||||
CLASS | Class 1 | Class 0.5 | Class 0.5S | Class 0.2 | Class 0.2S | Class 0.1 |
1000/5 A | 15 VA | 15 VA | 5 VA | 5 VA | - | - |
1200/5 A | 15 VA | 15 VA | 10 VA | 10 VA | - | - |
1250/5 A | 15 VA | 15 VA | 15 VA | 15 VA | 5 VA | - |
1500/5 A | 15 VA | 15 VA | 15 VA | 15 VA | 7.5 VA | - |
1600/5 A | 30 VA | 30 VA | 25 VA | 15 VA | 7.5 VA | - |
2000/5 A | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA |
2500/5 A | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA |
3000/5 A | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA |
3200/5 A | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA |
4000/5 A | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA | 30 VA |
Current Transformers Coding Map
Parameter | Value |
Standards | IEC 60044-1, IEC 61869-2, VDE 0414-1, DIN57414, BS3938, BS7626, EN 61869-2 |
CT Ratio | From 1000A to 4000A |
Rated Power | Up to 40VA |
Accuracy class | Class 1, 0.5, 0.5S, 0.2, 0.2S, 0.1 |
Terminal | İntegral terminal cover, high cross section brass terminal for extra safety |
Case | Non-flammable self-extinguishing ABS/PC |
Mounting | Various mounting options |
Ambient temperature (operation) | -25 C ~ +85 C |
Primary conductor | 100 x 30mm |
Round conductor | Ø 85mm |
Number of input | 1 |
Thermal rated short-time current | Ith = 60 * In or Ith=60kA |
Thermal rated continuous current | Id = 1 * In |
Rated frequency | 50 Hz … 60 Hz |
Surge current limitation factor | FS 5 |
Test voltage | 3 kV for 1 min |
Max system voltage | 0.8 kV |