- Generator Input and Generator Compensation
- Compensation for Inductive and Capacitive Systems
- Manual Step Value Enterable
- Single, Two and Three Phase Capacitor and Shunt Reactor can be connected
- Voltage, Harmonic Current/Voltage, Inductive and Capacitive Alarm Output
- Step Drive, Step Release, Discharge and Settlement Times are Adjustable
- Cosine/Power factor values of Each Phase Can Be Observed
- Step Drive, Step Release, Discharge and Settlement Times are Adjustable
- Capacitive/Active and Inductive/Active Ratios can be Observed
- Total Active and Reactive Energies (Import/Export/Inductive/Capacitive) can be Observed.
- THD-V and THD-I values of Each Phase can be Observed.
- Creating Power Analysis (20 samples 9999 min).
- It Shows The Total Number of Uses of the Steps.
- Encrypted Protection
- Same Aging in Steps
Parameter | Value |
Operating Voltage | 100V- 300VAC |
Operating Frequency | 50 / 60 Hz |
Operating Power | <14VA, <15VA (18-step models) |
Operating Temperature | -20°C…..55°C |
Storage Temperature | -30 °C….+88°C |
Voltage Measuring Range | 5V - 300V AC |
Current Measuring Range | 5mA - 5,5A |
Current Transformer Value | 5/5A to 5000/5A |
Voltage, Current Accuracy | %±0.5 |
Active Power Accuracy | %±1 |
Reactive Power Accuracy | %±2 |
Harmonic Voltage Measuring Range | 3 - 31 |
Harmonic Current Measuring Range | 3 - 31 |
Display | 2.9" (128×64) Graphic LCD and LEDs |
Connection Type | Plug-in terminal connection |
Contacts | 3A / 250V AC Resistive Load |
Generator Input Voltage | 230V AC 50/60 Hz. (Un %0,8-1,1) |
Cable Diameter | 1.5mm², 2.5mm² (Voltage Inputs) |
Weight | <900Gr |
Operating Altitude | <2000meters |
Protection Class | IP41 (Front Panel), IP20 (Body) |
Panel Hole Sizes | 140mm x 140mm |