| Compensation Programs | 7 porgrams, or manual compensation option |
| Automatic Step Measurement | Yes |
| Step Drive, Release and Discharge times | Adjustable |
| Voltage & Current Harmoncis alarm values | Adjustable |
| Over & under Compensation alarm Values | Adjustable |
| Alarm Output | Voltage, Harmonic Voltage/ Current, Over and under compensation |
| Fan output | Automatic |
| Monitering | Voltage, Current, Frequency, Active Power, Reactive Power, Apparent Power, THD-I, THD-V, Cos pi, PF, capacitive/active & Inductive/active ratios, Step Values |
| Parameter | Value |
| Operating Voltage | 100V- 300VAC |
| Operating Frequency | 50 / 60 Hz |
| Operating Power | <10VA |
| Operating Temperature | -20°C…..55°C |
| Voltage Measuring Range | 10V - 300V |
| Input Current | 10mA - 5,5A |
| Current Transformer Measuring Range | 5/5A to 10,000/5A |
| Cosine Measuring Range | 0 to 1 |
| Voltage, Current & Cosine Accuracy | %±1 |
| Active Energy Accuracy | %±2 |
| Reactive Energy Accuracy | %±2 |
| Contacts (Step Outputs) | 3A/250VAC Resistive load |
| Contacts (Fan & Alarm Output) | 3A/250VAC Resistive load |
| Number of steps | 12 Steps |
| Harmonic Voltage THD-V | Until 15th |
| Harmonic Current THD-I | Until 15th |
| Weight | <900Gr |
| Protection Class | IP41[Front Panel], IP20[Body] |
| Panel Hole Measurement | 140mm x 140mm |
| Connection Type | Plug-in Terminal Connection |
| Cable Diameter | 1.5mm², 2.5mm² for CT & Voltage connections |
| Mounting | Assembly to panel front cover |
| Working Altitude | <2000 meter |