Features

•Measures up to voltage harmonics 55th [L-N and L-L]

•Measures up to current harmonics 55th.

•3P3W supports 3P4W connections.

•RS485 Modbus RTU

•71.5 X 61.5 Custom Design Glass LCD.

•It shows the powers of each phase and total active [P1, P2, P3, P∑], total reactive [Q1, Q2, Q3, Q∑ inductive or capacitive] & total apparent powers [S1, S2, S3, S∑].

•It shows power factors [PF] and cos∑ values of each phases.

•It shows the minimum, maximum, and average values of the phase-to phase and phase-neutral voltages [V].

•It shows the values of each phase and total current [I1,I2,I3, I∑].

•It shows total import and export active [∑kWh] energy.

•2 relay outputs [adjustable], 1 Digital Input.

•Event logs [high voltage, low voltage, power interruption, voltage irregularity, high current, current irregularity, THDV and THDI limits].

•The date and time can be set.

•Real time clock.

•It shows demands.

•You can delete energies, demand, and event logs.

•The menu is password protected.

Technical Specifications
Operating Voltage 85V – 300 AC
Operating Frequency 50 / 60 Hz
Operating Power <10VA
Operating Temperature -20°C…..55°C
Input Voltage 5V – 330V AC
Voltage Measuring Range 1V – 600kV
Input Current 1mA – 5,5A
Current Measuring Range 1mA – 50.000A
Voltage, Current, Accuracy %±0,2
Active Accuracy %±0,5
Reactive Accuracy %± 1
Supported Connection 3P3W, 3P4W
Current Transformer Ratio 1….5000
Voltage Transformer Ratio 1,0….4000
Harmonic Voltage 3 – 55
Harmonic Current 3 – 55
Real Time Clock >5 year
Communication RS485 MODBUS RTU
Display 71.5 x 61.5mm Glass LCD
Contact Output 2A / 250V AC [Resistive Load]
Digital Input 9V – 24V DC
Weight <300Gr
Protection Class IP40[Front Panel], IP00[Body]
Panel Hole Measurement 91mm x 91mm
Connection Type Plug-in Terminal Connection
Cable Diameter 1.5mm²
Assembly Assembly to panel front cover
Working Altitude <2000 meter