Features

•RS485 Modbus RTU [1200 – 38400bps]

•71.5 x 61.5 Custom Design Glass LCD

•3-phase voltage and 3-phase current transformer.

•It shows that V,V2,V3,V12,V23,V31,I1,I2,I3,P1,P2,P3,S1,S2,S3,F1,F2,F3,kWh,∑kWh

•It shows the minimum, maximum and average values of V1,V2,V3,V12,V23,V31,F1,F2,F3

•It shows the maximum, average and demand values of I1,I2,I3,S1,S2,S3,P1,P2,P3

•Shows phase sequence

•You can delete the demands and active energy records

•Menu is password protected.

Technical Specifications

Operating Voltage 85V -240V AC
Operating Frequency 50 / 60 Hz
Operating Power <10VA
Operating Temperature -20°C…..55°C
Voltage Input 5V – 300V AC
Voltage Measurement Range 5V – 300kV
Current Input 50mA – 5,5A
Current Measurement Range 50mA – 10.000A
Voltage, Current, Accuracy %± 1
Supported Connection 3P4W
Current Transformer Ratio 1….2000
Voltage Transformer Ratio 1….999
Communication RS485 MODBUS RTU
Display 71.5 x 61.5mm Glass LCD
Output None
Weight <300Gr.
Protection Class IP40(Panel), IP00(Body)
Panel Hole Size 91mm x 91mm
Connection Type Plug-in Connection
Cable Diameter 1.5mm²
Installation Front panel mounted
Operating Altitude <2000m.