Parameter | Measured Values |
Total Harmonics Distorition | THD-V, THD-I |
Voltage Harmonics | Up to 31st harmonics (L-N and L-L] |
Current Harmonics | Up to 31st harmonics |
Active Power | P1, P2, P3 |
Reactive Power | Q1, Q2, Q3 |
Q | S1, S2, S3 |
Power Factor | True PF, cos φ (of each phase) |
Voltage | phase-to-phase |
phase-to-neutral | |
(min, max & average values are saved) | |
Current | I1, I2, I3, ΣI (min, max & demand are saved) |
Frequency | F1, F2 ,F3 (min, max & average) |
Energy | ∑kWh (import & export) |
∑kVARh (inductive & Capacitive) | |
Relay Output | adjustable |
Irregularties | voltage and current İmplances |
Communication | RS485 Modbus RTU |
Memory | You can delete energy values, demands records and event logs. |
Password | Menu is password protected |
Parameter | Value |
Operating Voltage | 85V - 240 AC |
Operating Frequency | 50 / 60 Hz |
Operating Power | <10VA |
Operating Temperature | -20°C…..55°C |
Input Voltage (L-N) | 5V - 330VAC |
Voltage Measuring Range | 5V - 330kV |
Input Current | 10mA - 5,5A |
Current Measuring Range | 10mA - 5500A |
Voltage, Current, Accuracy | %±0.5 |
Active Energy Accuracy | %±1 |
Reactive Energy Accuracy | %±2 |
Supported Connection | 3P4W |
Current Transformer Ratio | 1….1000 |
Voltage Transformer Ratio | 1,0….9999 |
Harmonic Voltage | 3 – 31 |
Harmonic Current | 3 – 31 |
Digital Input | 9V - 24V DC |
Weight | <300Gr |
Protection Class | IP41[Front Panel], IP20[Body] |
Panel Hole Measurement | 91mm x 91mm |
Connection Type | Plug-in Terminal Connection |
Cable Diameter | 1.5mm² |
Mounting | Assembly to panel front cover |
Working Altitude | <2000 meter |