- Measuring and Control Scale: -19.9 °C ±99.9 °C
- Microprocessor Based, PID Temperature Controller
- NTC Sensor Type
- ON-OFF Control Form
- OUT and ALARM Outputs
- Selectable Heating and Cooling Function
- Upper and Lower Limit for SET and ALARM Settings
- Adjustable Separate Hysteresis for SET and ALARM Settings
- Selectable Relative, Absolute or Band Alarm
- ON-delay for OUT in Cooling Mode
- Adjustable ON/OFF Timers for OUT Output in Case of Sensor Failure
- Input “Offset” Feature
- Excellent Linearity with °C/mV and °C/W Look-up Tables
- Password Protection
- High Accuracy
- EEPROM Memory to Store Settings
- Easy Connection with Plug-in Connectors
| Parameter | Measured Values |
| Dimensions | 35x77mm |
| Panel Cut-out | 29x71mm |
| Display | 3 Digits 7 Segment |
| Sensor Type | NTC |
| Measuring Scale | -19.9 to 99.9℃ |
| SET Interval | LoL .. UPL ℃ (HSt) |
| Hysteresis Interval | 0.1 to 20.0℃ |
| Alarm Interval | AtP = Abs, -Ab; LoL … UPL C (Ast) |
| Offset | -19.9 to 20.0 ℃ |
| Resolution | ± 0.1℃ |
| Accuracy | ±3% (Over full scale) |
| Control Form | ON-OFF |
| Heating/Cooling | H-C; HT (Heating), CL (Cooling); Selectable |
| Out & Alarm Output | Relay (NO + NC), 250VAC, 2A, Resistive load |
| Sensor Failure | Measurement out of range or Hardware fails, OUT outputting is first OFF for T0f and then ON for T0n periodically. For continuous OFF, enter T0n=0 and T0f=0. For continuous ON, enter T0n=1 and T0f=0. In case of sensor failure, measurement out of range or hardware fails, and alarm type is selected as “SnS”, ALARM output is always ON, otherwise under normal in scale measurement, always OFF |
| Supply Voltage | 100 to 240VAC, 50-60Hz |
| Power Consumption | < 6VA |
| Humidity | < 70% (non-condensing) |
| Altitude | < 2000m |
| EMC | EN 61000-6-1, EN 61000-6-3 |
| Safety | EN 61010-1 |
| Protection Class | IP20 |
| Operating Temperature | 0 to 50℃ |
| Storage Temperature | -10℃ to 60℃ |
| Weight | < 0.5 kg |
| Keys | Micro Switch |
| Torque for screwing | Max. 0.5Nm |